Home About Us Contact Us

Electric Heating

Air-Port Electric Heaters

Air-Port Portable Electric Heaters can be used for occupied spaces and process applications in both indoor and outdoor environments. These units are available in sizes ranging from 15 - 45 kW using a highly efficient fin-coil design. The air supply can be either ducted or freeblow and the slim horizontal design is easily transportable using casters or a fork-lift.


AIR-PORT PORTABLE ELECTRIC HEATERS

        Blower Motor      

Model

Nominal kW (a)

Voltage

Heater FLA (b)

HP

FLA

Min Circuit Amps

Circuit Breaker Amps

 

APH15G*E

15

208/230/3/60

460/3/60

32.8

17.1

1.5

1.5

4.4

2.2

47

24

60

30

 

APH30G*E

30

208/230/3/60

460/3/60

65.7

34.3

2

2

6

3

90

47

100

60

 

APH45G*E

45

208/230/3/60

460/3/60

98.5

51.4

3

3

8.2

4.1

133

69

175

80

 
(a) Heaters are nominal rated at 240/3/60 or 440/3/60  
(b) Full Load Amps (FLA) indicated at 230 or 460 volts  

Model

CFM  c

ESP

No. of Stages

BTUH (d)

BTUH (e)

Heater Type

Filter Type

Filter Qty/Size

Approx. Net Weight

APH15G*E

1100

N/A

1

52000

42000

Finned Tubular

Permanent Cleanable

1/35 x 12

415 lbs.

APH30G*E

2100

N/A

2

104000

84000

Finned Tubular

Permanent Cleanable

1/35 x 12

425 lb.s

APH45G*E

3100

N/A

2

156000

126000

Finned Tubular

Permanent Cleanable

1/35 x 12

435. bls.

(c) Based on nominal 45 deg F temperature rise
(d) BTUH at 230/460 volt power output
(e) BTUH at 208 volt power output

Unit Features Include:

Stages: 15 kW - 1 stage
  30 kW - 2 stage
  45 kW - 2 stage
Finned Tubular Heaters Guard on Return Air
Insulated Cabinet Blower Off Time Delay
Bumpers on Each Corner Handles
Belt Drive Centrifugal Blower Main Circuit Breaker
Power Indicator Light 5" Casters (swivel / locikable)
On / Off Switch Analog Thermostat (external)
Bi-Directional Discharge Grille Powder Coated Cabinet (White)
Fork Lift Pockets (front to back) Individual Circuit Breaker on Each Stage of Heat
Permanent Cleanable Filters Individual Contactor on Blower Motor and Each Stage of Heat
Air Flow Proving Switch High Limit Safety Switch